旁路功能
bypass
说明:当启动过程完成时,内置触点便会闭合;而停车信号发出时,内置触点便会打开。
Description: when the start process is completed, the built-in contacts will be closed; and when the parking signal is issued, the built-in contacts will open.
软起动结束,旁路接触器闭合,使软起动器退出运行,直至停车时,再次投入,这样即延长了软起动器的寿命,又使电网避免了谐波污染,还可减少软起动器中的晶闸管发热损耗。
Soft start end bypass contactor is closed, the soft starter is out of operation, until the stop, once again put into, so that prolong the life of the soft starter, but also to avoid network harmonic pollution, but also can reduce the thyristor soft starter in pipe heat loss.
在电控柜内还可实现由于软启动器的损坏而使用接触器“直接启动”的方式。不影响用户的正常生产。
In the cabinet can also be achieved due to damage of soft starter and the use of "direct contactor start" way. Does not affect the normal production of users.
如何实现电机保护功能
How to realize motor protection function
由于PSS系列软启动器没有内置电子过载保护器(PST/PSTB系列已经内置),需要在主回路增加热继电器实现过载保护功能,随时跟踪检测电机电流的变化状况。过载时,关断晶闸管并发出报警信号。
Since the PSS series soft starter has no built-in electronic overload protection device (PST/PSTB series has been built in the main loop), need to increase the thermal relay overload protection function, changes in tracking motor current detection. When overload, turn off the thyristor and send out alarm signal.