2区小主机消防火灾控制器迷你控制面板红色panel

  • 发布时间:2020-12-31 09:59:43,加入时间:2018年10月08日(距今2402天)
  • 地址:中国»广东»深圳:深圳市宝安区福永街道科技园
  • 公司:深圳市众安科电子有限公司, 用户等级:普通会员 已认证
  • 联系:宁,手机:15220176087 微信:zoanco-fa 电话:0755-23015236 QQ:3387459559

英文版2区小主机消防火灾控制器迷你控制面板红色(2 zones conventional fire alarm control panel)

1. Introduction

The information provided in this manual covers the Master and Slave fire alarm control panel. The panel range is designed to

meet the requirements of EN54 Parts 2 & 4.

The fire alarm control panels (2 Zones) provide all of the sophisticated features required of a leading edge conventional fire

alarm system along with the simple operation and efficient installation methods demanded by both installers and building

users.

A comprehensive range of auxiliary devices is available to operate with the fire control panels including optical, ionization,

photoelectric, photoelectric-thermal and heat detectors.

Each of the system components has been specifically designed to operate as part of the system. This provides assurance

that the control panel, smoke detectors, interface devices and the ancillary components are all fully compatible with one

another and that the full range of system functionality is supported by each device.

1.1 Product Features

The panels have the following key features:

conventional input zones.

notification appliance circuits (NAC) with built-in synchronization for ANSI 3.41and Gentex.

The panel comes with a 2 amp power supply.

Dedicated alarm and trouble relays.

RS485 can be able to connect the other panel.

Housed in a 205mm W x 258mm H x 81mm D metal enclosure.

Enclosure supports two 12V, 4Ah backup batteries.

The panel can be used independently or connect by RS485.

1.2 Electrical Specifications

Primary AC 120VAC 50/60 Hz Power supply rating

240VAC 50/60 Hz

Power supply rating 2 Amps 24VDC

Maximum Battery Charging Current 0.98 Amps 26VDC

Initiating Device Circuits 2 Zones Alarm Zone 2

Normal Initiating Operating Voltage 23VDC, Maximum 26VDC, regulated

Normal Quiescent Current (normal status) <50mA

Alarm Current (not include the others) <150 mA

Short Circuit Initiating Current (per zone) 35mA Maximum

Maximum Initiating Resistance (per zone) 10 ohms

Initiating End-of-Line Resistor 4K7 ohms, 1/2W 5%

Standby Detector Current (per zone) 4mA maximum

Maximum Detector Count (per zone) 30 detectors

Initiating Cabling Type 18AWG Twisted Shielded pair (14 – 18 AWG)

Detector Base Impedance 430 ohms

Notification Appliance Circuits 1 NACs, Special Application

Maximum NAC Current Rating 1 Amp maximum per circuit

NAC Operating Voltage 26VDC Nominal, 30VDC Maximum

NAC End-of-line Resistor 1N4007 Diode

FAULT Relay rating 2A & 30VAC, resistive

Alarm( Auxiliary ) Relay rating 2A & 30VAC, resistive

Master alarm panel Digital & LED display

Slave alarm panel LED display only